46 Important Product Information
GFK-1671P
Open Issues and Problems
Miscellaneous Issues
ID Description
CR74577
Grid Repainting issue when opening and closing many windows within VersaPro.
Details: If you open and close approximately 2200 or more windows within VersaPro, you
may notice that grids in certain Windows will not be re-drawn particularly if the window is
made larger.
Resolution: You can make the window smaller or close and re-open VersaPro.
CR75277
VersaPro doesn’t ensure that AUP file used with VersaMax CPUE05 or CPU374 is at or
less than 4KB or 12KB respectively in size for store.
Details: The maximum AUP size that will be accepted and used by the CPUE05 and CPU374
are 4KB and 16KB respectively. VersaPro will not warn you that the file is larger than this
limit when storing the file to the PLC. The PLC will either generate a fault or error if this is
attempted.
Resolution: When preparing an AUP file to store to the CPUE05 or CPU374, you should use
Windows Explorer to check the size of the file. If the size of the file is greater than the
prescribed limit, you should edit the file to reduce the size to less than or equal to the limit
before attempting to store the file to the PLC.
Password/OEM Key/Access Level Issues
ID Description
CR72614
Access Level 2 does not allow store of stored/override values.
Details:
1) Open any folder and connect to PLC
2) In status dialog, set access to level 2 (Write data level)
3) Do a store of Stored/Override values only
An error message will be presented “Store Error 0x0200-Insufficient Privilege Level” Stored
values should be allowed at level 2 but overrides require access level 3. This is also an issue
with Logicmaster since it does not allow selection of stored values and overrides separately.
Resolution: The access level must be set to level 3 or higher in order to store stored/override
values.
A locked block can be unlocked even if a character is typed wrongly
Details:
1) Edit/View Lock an LD or IL block using the Edit->Properties->Block->Lock dialog
2) Now when Unlocking the locked block, type the 4
th
character wrong.
The block gets unlocked. This may even happens with other letters in the password depending
on the length of the password.
Resolution: A password of 3 characters should be used to lock a block.