28 Important Product Information
GFK-1671P
Problems Resolved
ID Description
16880
A stop fault error is produced when the internal switch on ACC300 Input simulator
module is in 8-bit position
Details: ACC300 input simulator (switch module) contains 16 switches plus and internal
switch to disable the second group of 8 switches leaving only 8 switches active. VersaPro
allows the number of %I points to be either 8 or 16. This would indicate it is reading the
internal 8/16 switch position. With the internal switch in the 8 point option, a stop fault error
(config mismatch) is produced.
CR75970
Unable to delete GBC at SBA 31.
Details: If you try to delete the BEM731 in the slot 31 of a Genius Bus Controller, save and
reopen the hardware configuration the BEM731 reappears in the slot 31.
Resolution: The BEM731 in the slot 31 cannot be deleted in VersaPro 2.01
19039
Incorrect validation of Scan sets in 90-70 configuration
Details: Change the I/O Scan set for a 90-70 module to a value larger than the number of scan
sets defined in the Scan Sets Tab of 90-70 CPU configuration. Close the folder and you get an
error saying that the I/O Scan Set parameter value is incorrect. Reopen the folder and no error
is displayed.
Resolution: This is corrected in VersaPro 2.01. An error message will be displayed in the Log
View window when opening the invalid configuration.
19836
The value of the Length parameter in BBA100 module is incorrect
Details: The length parameter in the Settings Tab of BBA100 mixed analog 90-70 module is
wrongly set to 8. It’s value should be 4.
Resolution: This is corrected in VersaPro 2.01.
18841
Cut and Paste of modules from one slot to another in Hardware Configuration changes
the reference address values
Details: When a module is cut from one slot and pasted to another slot, the values of the
reference addresses are changed.
Resolution: The reference addresses are not auto-assigned in VersaPro 2.01and the same
reference addresses are retained on Cut and Paste. Conflict of reference addresses, if any, is
also flagged.
LM90 Folder Import issues resolved:
ID Description
CR75761
Import of a LM90 folder with redundant GBC pairs causes fatal overlaps
Details: If you import a Logicmaster 90-70 folder with two redundant pair Genius Bus
Controllers (GBC), VersaPro may declare there is a fatal overlap between the input points
(analog and discrete) on both GBCs. However, as a redundant pair, the I/O must be
programmed identically and a fatal overlap should not be declared.
18682
Import of a LM90 folder with APU305 configured changes %I reference address.
Details: When a LM90 folder with APU305 module configured is imported into VersaPro
2.00, the value of the %I starting reference address in the Settings Tab of APU305
configuration is changed.
Resolution:
This is resolved in VersaPro 2.01 and the correct value of the reference address is
generated.
CR75812
Import of a LM90 folder with Genius Global data may produce parameter error.
Details: If you import a Logicmaster 90-70 folder with Genius Global Data, look at the Global
Data tab on the Genius Bus Controller
(
GBC
)
and then tr
y
to close the bus controller